1. Do not install any of the products in this bulletin at pressures
or temperatures higher than the published ratings.
2. 450 Butyl, EPDM & Viton connectors are recommended for intermittent
(10 minute maximum exposure per hour) 250°F. service or continuous
service at a maximum of 225°F. Use Mercer series 500, 600, HT500
or HT600 as described in bulletin 500-MR7 for continuous temperatures
of 230°F and higher.
3. Series 450 must be installed against standard 1/16 raised faced
or flat faced flanges. Do not install them against recessed flanges
such as Victaulic without calling the factory for proper steel filler
flanges. If our rubber flanges do not have full bearing the expansion
joint will be damaged and leak or fail.
4. Initial misalignment should be kept to a minimum of 1/8.
5. Pipe system flanges must be smooth and flat. Screw in brass inserts
such as those used in check valves can damage the rubber faces if they
project above the cast flange face.
6. Water type check valves must exactly center on the rubber flanges.
Valve O.D. and I.D. should be checked for conformance with raised face
dimensions
7. Check Chemical Resistance
Guide CRG-MR1 for service elastomer compatibility.